NTC Thermistor Sensors for 150-200 °C

Which insulation systems hold 150 °C to 200 °C continuously, what this construction is rated to, and the control and cut-out that hold the surface there.

NTC Thermistor Sensors are rated 200 °C continuous, which covers 150 °C to 200 °C. The top of the flexible polymer range. Silicone rubber and polyimide both run continuously at 200 °C; above it both degrade, and no amount of derating changes that.

Working band
150 °C to 200 °C
Continuous limit, this construction
200 °C
Total thickness
Component
Maximum outline, one piece
Component

The band is the temperature the heated surface has to hold, not the temperature the element reaches. The element always runs hotter, by an amount the watt density and the thermal path decide, so the cut-out is set against the element and not against the load.

NTC Thermistor Sensors — the construction this guide is about

Duty temperature decides the construction before anything else does. At 150 °c to 200 °c, ntc thermistor sensors is a candidate; the sections below set out what it will hold, what has to be true for it to hold it, and what fails first when it does not.

What the 150 °C to 200 °C Band Requires

The top of the flexible polymer range. Silicone rubber and polyimide both run continuously at 200 °C; above it both degrade, and no amount of derating changes that.

Band150 °C to 200 °C
This construction, continuous200 °C

This band reaches the ceiling of the construction. At 200 °C there is no headroom left, so the control has to hold the set point rather than approach it from above, and the limit device has to be set where it can act before the insulation does. A duty that spends its time at the top of the band is a duty that should be quoted against the next construction up.

Why the Boundary Is Where It Is

200 °C is the top of the flexible polymer range. Silicone rubber and polyimide both run there continuously, and both degrade above it — silicone hardens and loses its tear strength, polyimide embrittles. No derating changes either.

Cross this line and the construction changes completely: fired thick film on stainless or alumina, or a mica-insulated element. Those parts are rigid, clamped and made to a different drawing, so the boundary is a redesign rather than a substitution.

What an NTC Thermistor Sensors Is

The 10K B3950 thermistor is the default sensor on a low voltage heater: cheap, sensitive, and readable by any microcontroller with one resistor.

A sensing component, specified by its tolerance class, its usable range and its response time. It has no watt density and no outline; it is fitted to a heater or to the surface the heater is warming, and where it is fitted decides what the control loop is actually controlling.

The heat leaves through whatever the component is clamped or bonded to; a sensing component adds no heat of its own and simply has to be in thermal contact with the thing it is reporting on.

Total thicknessComponent
Maximum size, one pieceComponent
Continuous working temperature200 °C

The continuous limit of 200 °C is set by the insulation system. The element alloy would run far hotter; it is never the element that decides.

Which Temperature Is Being Held

Three temperatures matter and they are not the same number: the element temperature, the temperature of the surface being heated, and the ambient. A heater rated for a continuous working temperature is rated at the element — the hottest point in the assembly, and the one nothing on the outside is measuring.

The gap between element and surface is the thermal path. Bonded to metal it may be a few degrees; across an air gap, a void in the adhesive or a dry clamped joint it can be tens of degrees, and every one of them appears at the element rather than at the load.

Control and Protection

This heater has no way of limiting its own temperature. Resistance heating draws roughly the same power whatever the temperature, so with the load removed, the fluid gone, the fan stopped or the sensor open circuit, the element keeps producing watts until something stops it.

The design must therefore contain a control device and, separately, a protective one: a controller with a sensor to hold the set point, and a bimetal thermostat or a one-shot thermal cutoff wired in series with the element to open the circuit if the loop ever fails. The two are not interchangeable — a controller that has lost its sensor cannot protect anything, which is exactly the fault the cutoff exists for.

How This Construction Fails

  • Loss of the control loop. An open-circuit sensor, a welded relay contact or a controller in manual leaves the element at full power with nothing watching it — the case the series thermal cutoff exists for, and the reason it must not be omitted to save a part.
  • Measuring the wrong thing. A sensor in the air near a heated plate reports the air, and the loop holds the air where the specification wanted the plate. Nothing in the instrument can detect this.

Other Constructions That Hold 150 °C to 200 °C

Constructions in this catalogue that will hold 150 °c to 200 °c continuously:

How to Specify One

This is a made-to-drawing part, so there is no catalogue number to quote. A quotation is built from the following, and the more of it that arrives with the enquiry the fewer rounds it takes:

  • The temperature to be sensed or switched, and the tolerance the application actually needs.
  • Where the component sits — against the element, in the potting, on the load, or in the airflow.
  • The electrical duty: for a switching device, the voltage, the current and whether the load is AC or DC.
  • Lead length, insulation and termination, and whether the component is fitted by us into a heater assembly or supplied loose.
  • The standard the end product is certified to, so the component chosen is one that fits inside that approval.

Lead time: Samples 7-10 days from approved drawing; production 15-20 days.

NTC Thermistor Sensors — Capability Table

These are process limits for the construction, not the specification of one stocked item. Every line is what the factory can hold; what your part holds is fixed on your drawing.

ParameterSpecificationLimit / note
TypeNegative temperature coefficient thermistorResistance falls as temperature rises, steeply
Standard part10 ku03a9 at 25 u00b0C, B25/50 = 3950 KThe value nearly every controller expects by default
Other values5 ku03a9, 50 ku03a9, 100 ku03a9; B values 3435 K to 4100 KChosen to match the controller, not the heater
Toleranceu00b11% resistance, u00b11% B valueu00b10.5 u00b0C interchangeable parts available
Temperature range-40 u00b0C to +200 u00b0C depending on encapsulationEpoxy bead to +125 u00b0C, glass bead to +200 u00b0C
Response time1 to 10 seconds depending on mass and mountingMounting dominates: a sensor in air reads air
EncapsulationEpoxy bead, glass bead, or laminated into the heaterLaminated is what makes it read the element
LeadsPTFE or silicone insulated, to your length and termination

Figures are the published tolerance and rating bands of the standard sensor and control components fitted to these heaters. Sensor tolerance classes follow IEC 60751 for RTDs and IEC 60584 for thermocouples; thermostat and thermal cutoff ratings are the component manufacturers' own.

Outline & Specification Builder

Set the outline, the size, the voltage and the power you have in mind. The drawing redraws to match, and the panel works out the heated area, the watt density and the current — then checks that watt density against what this construction survives in free air and bonded to a heat sink. Those two limits are different by several times, and it is the difference that decides whether a heater lasts.

Fills in the form below; attach your outline drawing or DXF there.
Our facility

Held in production, not just on paper

The limits above are the ones our own lamination press, die and test lines actually hold, and every unit is tested rather than a sample. A figure is only worth quoting if it survives the process that produces it.

Insulation film fed from the roll
Vulcanising press closing on a lay-up
Heater outlines being die cut
Finished heaters batched for dispatch

Request a Quote

The form below follows the current technical drawing configuration. Change the drawing values above and the request details update automatically.

Request a Quotation

The part

If you have an outline drawing or a DXF, say so in the notes and we will reply with an address to send it to — a drawing turns an estimate into a quotation.

Business Information

Dimensions & Specifications (IEC 60730 / IEC 60335 / RoHS)

ParameterSpecificationLimit / note
TypeNegative temperature coefficient thermistorResistance falls as temperature rises, steeply
Standard part10 ku03a9 at 25 u00b0C, B25/50 = 3950 KThe value nearly every controller expects by default
Other values5 ku03a9, 50 ku03a9, 100 ku03a9; B values 3435 K to 4100 KChosen to match the controller, not the heater
Toleranceu00b11% resistance, u00b11% B valueu00b10.5 u00b0C interchangeable parts available
Temperature range-40 u00b0C to +200 u00b0C depending on encapsulationEpoxy bead to +125 u00b0C, glass bead to +200 u00b0C
Response time1 to 10 seconds depending on mass and mountingMounting dominates: a sensor in air reads air
EncapsulationEpoxy bead, glass bead, or laminated into the heaterLaminated is what makes it read the element
LeadsPTFE or silicone insulated, to your length and termination

Video: NTC Thermistor Sensors for 150-200 °C

Third-party video, selected automatically for this topic. It is not produced by Heating Film and is not a specification source — use the tables on this page for dimensional data.

Frequently Asked Questions

What is the maximum temperature of ntc thermistor sensors?

200 °C continuous, measured at the element. The limit belongs to the insulation system and not to the element alloy, so it is not a figure that can be extended by derating the power.

Does this heater need a thermostat?

Yes. It has no mechanism for limiting its own temperature — with the load removed or the control loop failed it keeps producing the same power — so the design needs a controller with a sensor to hold the set point and, separately, a bimetal thermostat or a one-shot thermal cutoff in series with the element as protection.

How large can one piece be?

Component in a single piece. Larger areas are supplied as tiled zones with separate circuits, which is usually better engineering anyway: separate zones can be controlled separately, and a large single circuit has to carry the whole current at one lead exit.

Which heaters work at 150 °c to 200 °c?

The top of the flexible polymer range. Silicone rubber and polyimide both run continuously at 200 °C; above it both degrade, and no amount of derating changes that.

How do I request a quotation?

Send the outline drawing with the supply voltage, the power or the target temperature, what the heater is bonded to, the ambient and the duty cycle. We respond within one business day.