Which insulation systems hold 150 °C to 200 °C continuously, what this construction is rated to, and the control and cut-out that hold the surface there.

Digital and PID Temperature Controllers are rated 400 °C continuous, which covers 150 °C to 200 °C. The top of the flexible polymer range. Silicone rubber and polyimide both run continuously at 200 °C; above it both degrade, and no amount of derating changes that.

Working band
150 °C to 200 °C
Continuous limit, this construction
400 °C
Total thickness
Component
Maximum outline, one piece
Component

The band is the temperature the heated surface has to hold, not the temperature the element reaches. The element always runs hotter, by an amount the watt density and the thermal path decide, so the cut-out is set against the element and not against the load.

Digital and PID Temperature Controllers — the construction this guide is about

The 150 °c to 200 °c band is a material boundary, not a convention. The top of the flexible polymer range. Silicone rubber and polyimide both run continuously at 200 °C; above it both degrade, and no amount of derating changes that. This page covers what that means for digital and pid temperature controllers, which is rated to 400 °C continuous.

What the 150 °C to 200 °C Band Requires

The top of the flexible polymer range. Silicone rubber and polyimide both run continuously at 200 °C; above it both degrade, and no amount of derating changes that.

Band150 °C to 200 °C
This construction, continuous400 °C

The band sits comfortably inside the 400 °C ceiling, which is where a heater should be specified: the margin between the working temperature and the insulation limit is what absorbs a poor thermal path, a warm ambient and a control overshoot without shortening the life of the part.

Why the Boundary Is Where It Is

200 °C is the top of the flexible polymer range. Silicone rubber and polyimide both run there continuously, and both degrade above it — silicone hardens and loses its tear strength, polyimide embrittles. No derating changes either.

Cross this line and the construction changes completely: fired thick film on stainless or alumina, or a mica-insulated element. Those parts are rigid, clamped and made to a different drawing, so the boundary is a redesign rather than a substitution.

What a Digital and PID Temperature Controllers Is

Panel controllers to close the loop around the heater: on/off for simple holding, PID where the set point has to be reached without overshoot.

The instrument that closes the loop: it reads a sensor, compares it with a set point and switches the heater. It is what gives a heating system an accuracy figure — no heater has one on its own.

The heat leaves through whatever the component is clamped or bonded to; a sensing component adds no heat of its own and simply has to be in thermal contact with the thing it is reporting on.

Total thicknessComponent
Maximum size, one pieceComponent
Continuous working temperature400 °C

The continuous limit of 400 °C is set by the insulation system. The element alloy would run far hotter; it is never the element that decides.

Which Temperature Is Being Held

Three temperatures matter and they are not the same number: the element temperature, the temperature of the surface being heated, and the ambient. A heater rated for a continuous working temperature is rated at the element — the hottest point in the assembly, and the one nothing on the outside is measuring.

The gap between element and surface is the thermal path. Bonded to metal it may be a few degrees; across an air gap, a void in the adhesive or a dry clamped joint it can be tens of degrees, and every one of them appears at the element rather than at the load.

Attachment and Thermal Contact

A sensing component is fitted where it will read the temperature that matters: against the element for a limit device, against the load for a control device. The two positions give different numbers, and choosing the wrong one is the commonest reason a correctly built loop holds the wrong temperature.

A sensor reads its own junction, not the surface it is near. Bed it in thermal compound, clamp it, or pot it into the assembly: an air gap of a tenth of a millimetre between a thermistor and the plate it is supposed to be measuring is worth several degrees of error, and it is an error the controller cannot see.

Control and Protection

This heater has no way of limiting its own temperature. Resistance heating draws roughly the same power whatever the temperature, so with the load removed, the fluid gone, the fan stopped or the sensor open circuit, the element keeps producing watts until something stops it.

The design must therefore contain a control device and, separately, a protective one: a controller with a sensor to hold the set point, and a bimetal thermostat or a one-shot thermal cutoff wired in series with the element to open the circuit if the loop ever fails. The two are not interchangeable — a controller that has lost its sensor cannot protect anything, which is exactly the fault the cutoff exists for.

Where This Construction Is the Wrong Answer

  • Do not plan on running above 400 °C. That ceiling belongs to the insulation system, not to the element alloy, and it is not a figure that derating extends — past it the insulation degrades and the dielectric strength goes with it.
  • Do not rate this component as though it were the heater. It carries a contact rating or a tolerance class; the heater next to it decides the power, the watt density and the temperature the assembly reaches.

Other Constructions That Hold 150 °C to 200 °C

Constructions in this catalogue that will hold 150 °c to 200 °c continuously:

How to Specify One

This is a made-to-drawing part, so there is no catalogue number to quote. A quotation is built from the following, and the more of it that arrives with the enquiry the fewer rounds it takes:

  • The temperature to be sensed or switched, and the tolerance the application actually needs.
  • Where the component sits — against the element, in the potting, on the load, or in the airflow.
  • The electrical duty: for a switching device, the voltage, the current and whether the load is AC or DC.
  • Lead length, insulation and termination, and whether the component is fitted by us into a heater assembly or supplied loose.
  • The standard the end product is certified to, so the component chosen is one that fits inside that approval.

Lead time: Samples 7-10 days from approved drawing; production 15-20 days.

Digital and PID Temperature Controllers — Capability Table

These are process limits for the construction, not the specification of one stocked item. Every line is what the factory can hold; what your part holds is fixed on your drawing.

ParameterSpecificationLimit / note
Control modesOn/off, PID with autotune, ramp/soak programmesOn/off is adequate for a lagged mass and hopeless for a thin plate
InputPT100, PT1000, NTC, thermocouple type K/J/T/EConfigurable at the front panel
Control accuracyu00b10.1% of span, u00b11 digitOf the instrument u2014 the loop is only as good as the sensor placement
OutputRelay 3 A, SSR drive 12 V DC, 4-20 mASSR drive for anything cycling faster than once a minute
AlarmsHigh, low, deviation, sensor breakSensor break must fail the heater off, and this should be verified rather than assumed
Supply100-240 V AC or 24 V DC
Panel size48x48, 72x72, 96x96 mm DIN
StandardIEC 60730 / IEC 61010Controller safety and functional standards

Figures are the published tolerance and rating bands of the standard sensor and control components fitted to these heaters. Sensor tolerance classes follow IEC 60751 for RTDs and IEC 60584 for thermocouples; thermostat and thermal cutoff ratings are the component manufacturers' own.

Outline & Specification Builder

Set the outline, the size, the voltage and the power you have in mind. The drawing redraws to match, and the panel works out the heated area, the watt density and the current — then checks that watt density against what this construction survives in free air and bonded to a heat sink. Those two limits are different by several times, and it is the difference that decides whether a heater lasts.

Fills in the form below; attach your outline drawing or DXF there.
Our facility

The numbers come off our own machines

Every unit is measured for resistance, held at its dielectric test voltage for a minute, and measured again for insulation resistance. Sample units from each lot are run under power and imaged. That is why the values on this page are quotable rather than indicative.

Insulation film fed from the roll
Vulcanising press closing on a lay-up
Heater outlines being die cut
Finished heaters batched for dispatch

Request a Quote

The form below follows the current technical drawing configuration. Change the drawing values above and the request details update automatically.

Request a Quotation

The part

If you have an outline drawing or a DXF, say so in the notes and we will reply with an address to send it to — a drawing turns an estimate into a quotation.

Business Information

Dimensions & Specifications (IEC 60730 / IEC 60751 / IEC 60584)

ParameterSpecificationLimit / note
Control modesOn/off, PID with autotune, ramp/soak programmesOn/off is adequate for a lagged mass and hopeless for a thin plate
InputPT100, PT1000, NTC, thermocouple type K/J/T/EConfigurable at the front panel
Control accuracyu00b10.1% of span, u00b11 digitOf the instrument u2014 the loop is only as good as the sensor placement
OutputRelay 3 A, SSR drive 12 V DC, 4-20 mASSR drive for anything cycling faster than once a minute
AlarmsHigh, low, deviation, sensor breakSensor break must fail the heater off, and this should be verified rather than assumed
Supply100-240 V AC or 24 V DC
Panel size48x48, 72x72, 96x96 mm DIN
StandardIEC 60730 / IEC 61010Controller safety and functional standards

Video: Digital and PID Temperature Controllers for 150-200 °C

RTD calibrator/ RTD Simulator/ RTD Pt-100 source manufactured by Ace Instruments

Third-party video, selected automatically for this topic. It is not produced by Heating Film and is not a specification source — use the tables on this page for dimensional data.

Frequently Asked Questions

Is the temperature rating the surface temperature or the element temperature?

The element temperature, which is the hottest point in the assembly and the one nothing on the outside is measuring. The surface being heated sits below it by whatever the thermal path costs — a few degrees through a good bond, tens of degrees across a void or a dry clamped joint.

What is the maximum temperature of digital and pid temperature controllers?

400 °C continuous, measured at the element. The limit belongs to the insulation system and not to the element alloy, so it is not a figure that can be extended by derating the power.

Does this heater need a thermostat?

Yes. It has no mechanism for limiting its own temperature — with the load removed or the control loop failed it keeps producing the same power — so the design needs a controller with a sensor to hold the set point and, separately, a bimetal thermostat or a one-shot thermal cutoff in series with the element as protection.