Aramid Paper (Nomex type) PT100 and PT1000 RTD Sensors

What this insulation holds continuously, how thick the finished part is, the watt density it takes in free air and bonded, and where it stops being the right choice.

Aramid Paper (Nomex type) — To +180 °C continuous. A thin, tough, low-cost flexible insulation used where polyimide is unnecessary and silicone is too thick, mostly in transformer and appliance heating.

Insulation system
Aramid Paper (Nomex type)
Temperature range
To +180 °C continuous
Where it stops
Absorbs moisture, and its dielectric strength falls when it does.
Continuous temperature limit
400 °C continuous
Total thickness
Component
Maximum outline, one piece
Component

The temperature ceiling belongs to the insulation, not to the element: the resistance alloy would run far hotter, and it is the insulation around it that fails first. Figures are for the insulation system as built here; a part is quoted against the drawing, not against this table.

PT100 and PT1000 RTD Sensors — the construction this guide is about

Aramid Paper (Nomex type) is chosen for pt100 and pt1000 rtd sensors before anything else about the part is decided. A thin, tough, low-cost flexible insulation used where polyimide is unnecessary and silicone is too thick, mostly in transformer and appliance heating. The consequences — thickness, flexibility, what it survives and what it does not — follow below.

Aramid Paper (Nomex type) as an Insulation System

A thin, tough, low-cost flexible insulation used where polyimide is unnecessary and silicone is too thick, mostly in transformer and appliance heating.

Working rangeTo +180 °C continuous
Total thickness in this constructionComponent
Maximum size, one pieceComponent

A flexible insulation has to do three jobs at once: hold off the supply voltage, survive the element temperature, and bend without cracking. Thickness trades against all three — a thinner build responds faster and conforms better, and has less material between the element and whatever the heater is touching.

The Temperature Ceiling, and What Sets It

Working range: To +180 °C continuous. The ceiling belongs to the insulation. Nichrome will run red; aramid paper (nomex type) will not, and it is the material around the element that decides what the part is rated at.

This construction is rated 400 °C continuous. That is a continuous figure at the element, not an ambient and not a surface temperature measured somewhere convenient — and it is not a figure that derating extends downwards from something higher. Past the ceiling the insulation degrades, the dielectric strength falls with it, and the failure is electrical rather than thermal.

The boundaries across this catalogue are all material boundaries: PET stops at 120 °C, filled epoxy at 150 °C, silicone rubber and polyimide at 200 °C, and above that only fired and inorganic systems — thick film on stainless or alumina, and mica — are candidates at all.

What Attacks Aramid Paper (Nomex type)

Absorbs moisture, and its dielectric strength falls when it does.

What a PT100 and PT1000 RTD Sensors Is

Platinum resistance sensors for anything that has to be accurate, repeatable and calibratable — process plates, medical warming, and any loop that gets validated.

A sensing component, specified by its tolerance class, its usable range and its response time. It has no watt density and no outline; it is fitted to a heater or to the surface the heater is warming, and where it is fitted decides what the control loop is actually controlling.

The heat leaves through whatever the component is clamped or bonded to; a sensing component adds no heat of its own and simply has to be in thermal contact with the thing it is reporting on.

Total thicknessComponent
Maximum size, one pieceComponent
Continuous working temperature400 °C

The continuous limit of 400 °C is set by the insulation system. The element alloy would run far hotter; it is never the element that decides.

Above Its Ceiling: What to Use Instead

Aramid paper is a 180 °C insulation used where polyimide is unnecessary and silicone is too thick. Above it, silicone rubber and polyimide both reach 200 °C; above 200 °C the polymers stop altogether and the construction changes to a fired or mica-insulated one. Its weakness is moisture — it absorbs it, and its dielectric strength falls when it does — so a damp installation is a reason to move to silicone even well below the temperature limit.

Attachment and Thermal Contact

A sensing component is fitted where it will read the temperature that matters: against the element for a limit device, against the load for a control device. The two positions give different numbers, and choosing the wrong one is the commonest reason a correctly built loop holds the wrong temperature.

A sensor reads its own junction, not the surface it is near. Bed it in thermal compound, clamp it, or pot it into the assembly: an air gap of a tenth of a millimetre between a thermistor and the plate it is supposed to be measuring is worth several degrees of error, and it is an error the controller cannot see.

Control and Protection

This heater has no way of limiting its own temperature. Resistance heating draws roughly the same power whatever the temperature, so with the load removed, the fluid gone, the fan stopped or the sensor open circuit, the element keeps producing watts until something stops it.

The design must therefore contain a control device and, separately, a protective one: a controller with a sensor to hold the set point, and a bimetal thermostat or a one-shot thermal cutoff wired in series with the element to open the circuit if the loop ever fails. The two are not interchangeable — a controller that has lost its sensor cannot protect anything, which is exactly the fault the cutoff exists for.

T

h

How This Construction Fails

  • Loss of the control loop. An open-circuit sensor, a welded relay contact or a controller in manual leaves the element at full power with nothing watching it — the case the series thermal cutoff exists for, and the reason it must not be omitted to save a part.
  • Measuring the wrong thing. A sensor in the air near a heated plate reports the air, and the loop holds the air where the specification wanted the plate. Nothing in the instrument can detect this.

Where This Construction Is the Wrong Answer

  • Do not plan on running above 400 °C. That ceiling belongs to the insulation system, not to the element alloy, and it is not a figure that derating extends — past it the insulation degrades and the dielectric strength goes with it.
  • Do not rate this component as though it were the heater. It carries a contact rating or a tolerance class; the heater next to it decides the power, the watt density and the temperature the assembly reaches.

How to Specify One

This is a made-to-drawing part, so there is no catalogue number to quote. A quotation is built from the following, and the more of it that arrives with the enquiry the fewer rounds it takes:

  • The temperature to be sensed or switched, and the tolerance the application actually needs.
  • Where the component sits — against the element, in the potting, on the load, or in the airflow.
  • The electrical duty: for a switching device, the voltage, the current and whether the load is AC or DC.
  • Lead length, insulation and termination, and whether the component is fitted by us into a heater assembly or supplied loose.
  • The standard the end product is certified to, so the component chosen is one that fits inside that approval.

Lead time: Samples 7-10 days from approved drawing; production 15-20 days.

PT100 and PT1000 RTD Sensors — Capability Table

These are process limits for the construction, not the specification of one stocked item. Every line is what the factory can hold; what your part holds is fixed on your drawing.

ParameterSpecificationLimit / note
TypeThin film platinum resistance temperature detectorNearly linear, and its characteristic is defined by standard
StandardIEC 60751, class AA / A / BClass A is u00b10.15 u00b0C at 0 u00b0C; class B is u00b10.3 u00b0C
Nominal resistance100 u03a9 (PT100) or 1000 u03a9 (PT1000) at 0 u00b0CPT1000 is preferred on long low-voltage runs: lead resistance matters ten times less
Temperature range-50 u00b0C to +400 u00b0CThe element itself; the leads and potting are usually the limit
Wiring2, 3 or 4 wire2-wire adds the lead resistance to the reading u2014 use 3-wire beyond a metre
Self heatingKeep the measuring current at or below 1 mAA sensor heated by its own excitation current reads high, consistently
EncapsulationLaminated into the heater, in a stainless probe, or surface bonded
CalibrationCertificate traceable to national standards on requestRequired for validated processes

Figures are the published tolerance and rating bands of the standard sensor and control components fitted to these heaters. Sensor tolerance classes follow IEC 60751 for RTDs and IEC 60584 for thermocouples; thermostat and thermal cutoff ratings are the component manufacturers' own.

Outline & Specification Builder

Set the outline, the size, the voltage and the power you have in mind. The drawing redraws to match, and the panel works out the heated area, the watt density and the current — then checks that watt density against what this construction survives in free air and bonded to a heat sink. Those two limits are different by several times, and it is the difference that decides whether a heater lasts.

Fills in the form below; attach your outline drawing or DXF there.
Our facility

Where these heaters are actually made

Circuit layout, element preparation, lamination and vulcanising, die cutting and lead attachment all happen under one roof, so a watt density limit and a temperature ceiling are set by processes we control and can evidence, not by whichever supplier had stock.

Insulation film fed from the roll
Vulcanising press closing on a lay-up
Heater outlines being die cut
Finished heaters batched for dispatch

Request a Quote

The form below follows the current technical drawing configuration. Change the drawing values above and the request details update automatically.

Request a Quotation

The part

If you have an outline drawing or a DXF, say so in the notes and we will reply with an address to send it to — a drawing turns an estimate into a quotation.

Business Information

Dimensions & Specifications (IEC 60751 / IEC 60730 / RoHS)

ParameterSpecificationLimit / note
TypeThin film platinum resistance temperature detectorNearly linear, and its characteristic is defined by standard
StandardIEC 60751, class AA / A / BClass A is u00b10.15 u00b0C at 0 u00b0C; class B is u00b10.3 u00b0C
Nominal resistance100 u03a9 (PT100) or 1000 u03a9 (PT1000) at 0 u00b0CPT1000 is preferred on long low-voltage runs: lead resistance matters ten times less
Temperature range-50 u00b0C to +400 u00b0CThe element itself; the leads and potting are usually the limit
Wiring2, 3 or 4 wire2-wire adds the lead resistance to the reading u2014 use 3-wire beyond a metre
Self heatingKeep the measuring current at or below 1 mAA sensor heated by its own excitation current reads high, consistently
EncapsulationLaminated into the heater, in a stainless probe, or surface bonded
CalibrationCertificate traceable to national standards on requestRequired for validated processes

Video: Aramid Paper (Nomex type) PT100 and PT1000 RTD Sensors

Third-party video, selected automatically for this topic. It is not produced by Heating Film and is not a specification source — use the tables on this page for dimensional data.

Frequently Asked Questions

Does this heater need a thermostat?

Yes. It has no mechanism for limiting its own temperature — with the load removed or the control loop failed it keeps producing the same power — so the design needs a controller with a sensor to hold the set point and, separately, a bimetal thermostat or a one-shot thermal cutoff in series with the element as protection.

How large can one piece be?

Component in a single piece. Larger areas are supplied as tiled zones with separate circuits, which is usually better engineering anyway: separate zones can be controlled separately, and a large single circuit has to carry the whole current at one lead exit.

What temperature will Aramid Paper (Nomex type) stand?

To +180 °C continuous. That range is the insulation system's, and on a heater the insulation system is what sets the rating — the element will always outlast the material around it.

What are the weaknesses of Aramid Paper (Nomex type)?

Absorbs moisture, and its dielectric strength falls when it does.

How do I request a quotation?

Send the outline drawing with the supply voltage, the power or the target temperature, what the heater is bonded to, the ambient and the duty cycle. We respond within one business day.